Common Faults with Gledhill Systemate 2000
Common Faults and Troubleshooting Guide for Gledhill Systemate 2000 System
Note: All repair works must be performed by a qualified engineer. Refer to the Gledhill Systemate 2000 manual for detailed instructions.
Download Here : Gledhill SysteMate 2000 Manual
Buy Gledhill SysteMate 2000 Parts & Spares Here
Common Customer Complaints:
- The system is noisy
- Hot water service is unsatisfactory
- Space heating is unsatisfactory
Causes of a ‘Noisy’ System:
-
Noisy pump operation:
- Check F & E cistern water level, adjust if necessary, and vent the plate heat exchanger pump and system.
- Adjust pressure in the heating/primary system and vent if needed.
- Check boiler pump speed setting and adjust if required, ensuring temperature rise across the boiler does not exceed 11°C.
- Check heating pump speed setting and adjust if needed, ensuring temperature difference across flow and return does not exceed 11°C.
- Adjust heating system bypass valve if necessary.
- Ensure radiators are correctly balanced.
-
Noisy boiler operation:
- Check flow rate through the boiler and adjust pump speed if temperature rise exceeds 11°C.
- Adjust pressure in the heating/primary system if necessary and vent the system if needed.
-
Noise when hot water tap is opened:
- Check F & E cistern water level and vent pump if noisy.
- Address water hammer issues such as loose pipework and tap washers.
Causes of ‘Unsatisfactory Hot Water Service’:
- Ensure Systemate is full of water.
- Check boiler thermostat and set to maximum.
- Verify boiler flow temperature is adequate when firing stops.
- Check store is charging to at least 73°C.
- Ensure hot water plate heat exchanger pump operates when tap is opened and stops shortly after closing.
- Ensure plate heat exchanger pump is set at maximum speed.
- Confirm space heating and hot water load is not greater than boiler output.
- If all checks are satisfactory, consider scale buildup affecting heat exchanger performance.
Causes of ‘Unsatisfactory Space Heating’:
- Check boiler thermostat and set to maximum.
- Ensure boiler flow temperature before switching off is not less than 80°C.
- Check operation and settings of heating programmer and room thermostat.
- Verify heating system pump is circulating water to radiator circuit.
- Balance system, adjust pump speed, and check thermostatic radiator valves if some rooms are not heated properly.
Overflow from Feed and Expansion Cistern:
- Check water level in cistern and adjust if necessary to prevent overflow.
Appliance Control Board Check:
- Use switches SW1 and SW2 to establish/check operating and set temperatures, and identify faults on sensors.
- Refer to manual for detailed instructions.
Powerflushing/Cleaning of Heating System:
- Isolate Systemate appliance from heating system before powerflushing to prevent damage.
- Follow manufacturer's instructions for powerflushing equipment.
- Consult technical helpline if in doubt.
By following these steps and referring to the manual, technicians can effectively diagnose and address issues with the Gledhill Systemate 2000 system.